What C1, C2, C3 and FI mean on an EICR, how to decide between C2 and C3, and how the codes set the overall result, with a worked example.
The four codes on an EICR are C1 (danger present), C2 (potentially dangerous), C3 (improvement recommended) and FI (further investigation required). Any C1, C2 or FI makes the overall result Unsatisfactory. An installation with only C3s, or no observations at all, can be Satisfactory.
The hard part is rarely the definitions. It's deciding whether a missing RCD, a cracked socket or an odd bonding conductor is a C2 or a C3, and being able to defend that choice later. This guide covers how to make that call, where your judgement is the deciding factor, and how the codes feed the final result.
One caveat first. Zappy sells certificate software, so we have a commercial interest in how you complete EICRs. The coding advice below doesn't depend on any software. Where this article points you to a regulation or guidance document rather than quoting a number, that's deliberate: check the exact wording in your own copy.
| Code | Meaning | What you do | Effect on result | |---|---|---|---| | C1 | Danger present, risk of injury | Immediate remedial action required. Make safe on site where you can, and tell the person ordering the report | Unsatisfactory | | C2 | Potentially dangerous | Urgent remedial action required | Unsatisfactory | | C3 | Improvement recommended | Client decides whether to act | Does not make it Unsatisfactory on its own | | FI | Further investigation required without delay | Investigate further, as the observation can't be coded until you know more | Unsatisfactory |
These definitions come from the Model Forms in BS 7671 and are explained in IET Guidance Note 3 (Inspection and Testing). Use the wording in your current copy on the certificate itself.
The current standard is BS 7671:2018+A4:2026 (Amendment 4), published 15 April 2026. It supersedes BS 7671:2018+A2:2022+A3:2024, which was withdrawn on 15 October 2026. The IET treats Amendment 2 as obsolete for new work, certification and compliance references. If your certificate templates still quote Amendment 2, update them.
Here's the point that trips people up. BS 7671 is not retrospective. The IET has made clear that an installation which complied with the edition in force when it was installed is not automatically unsafe, and so doesn't automatically fail the Electricity at Work Regulations 1989. That is why coding is a two-step job:
• Establish what the installation was built to, as far as you can tell (age, markings, previous paperwork).
• Ask whether, as it stands today, it presents danger or potential danger.
A departure from the current edition is not by itself a C2. Compare it with the current standard to see what's different, then use your judgement and guidance such as IET Best Practice Guide 4 on classification codes to decide how serious it is in context.
We haven't confirmed what, if anything, Amendment 4 changed in the areas below. Read the Amendment 4 text for the RCD and bonding requirements before you rely on any older coding habits.
C1 means there's a risk of injury now. Typical examples are exposed live conductors that someone could touch, a burning smell from a hot accessory, or a bare live part in a damaged enclosure within reach.
What you do on site matters as much as the code:
• Make it safe if you can (isolate the circuit, cover or remove the live part) and say what you did.
• If the client won't let you isolate, record that, and tell them in writing.
• Still code it C1 even if you made it safe. The code describes the condition found.
• Don't leave a C1 live and walk away.
If you're hesitating between C1 and C2, ask whether someone could be hurt by normal use today without anything else going wrong. If yes, C1.
C2 is for something that isn't dangerous on its own but becomes dangerous if a second thing happens, such as a fault, a person touching something, or a cable being damaged. C3 is for something that falls short of current practice but doesn't present that kind of potential danger.
Four questions help:
• Is any live part accessible, or could it become so in normal use?
• If a fault happened, would the protective measures still work in time?
• Does the defect remove a protective measure altogether, rather than weaken it?
• Could you defend a C3 in writing if the installation were later investigated?
If the answer to 1 or 3 is yes, you're almost always in C2 territory. If the protective measure is present but sub-optimal, C3 is more likely.
These are typical starting points, not rules. Check Best Practice Guide 4, your scheme provider's guidance and the Amendment 4 text, and let the actual condition on site decide.
| Finding | Typical code | What shifts it | |---|---|---| | No RCD on socket circuits, older installation, no sign sockets feed outdoor equipment | C3 | C2 where sockets could reasonably supply portable equipment outdoors, or the installation is in a high-risk location | | No RCD protection on cables concealed in walls where the requirements applied at installation | Often C2 | Depends on installation date and cable depth; verify against the edition it was built to | | Cracked socket, live parts not accessible | C2 or C3 | Depth of crack, whether the front plate can be broken further, whether a child could reach it | | Cracked or broken accessory with live parts accessible | C2, or C1 if touchable | Whether someone can contact live parts now | | Missing main protective bonding to gas or water | C2 | Check whether the metalwork is actually extraneous | | Bonding present but undersized | C3 usually | Measured resistance, installation age, and what the requirements said at the time | | Missing consumer unit cover or blanks | C2 | Whether live parts are accessible | | Non-compliant but sound old wiring colours | C3 | Mixed colours or no labelling can raise it |
A socket circuit built before RCD protection for general sockets became standard practice isn't automatically dangerous. Plenty of installations have been fine for decades. The common approach is C3, because RCD protection is an additional protective measure and the installation complied when built.
Judgement moves it to C2 when the conditions make the missing RCD more serious: sockets in a garage that realistically feed a mower or hedge trimmer, outdoor use, a rental where tenants will plug in anything, or evidence that cables are buried in walls without mechanical protection. Look at the regulation on additional protection by RCDs in the Amendment 4 text and check what it says today.
Look at the accessory, not just the label. A hairline crack across a faceplate with no live part visible is a different finding from a socket with the front broken off. For a cracked socket, ask what happens if someone pushes a plug in hard or leans a bed against it. If the crack could expose live parts under normal use, C2. If it's cosmetic and the live parts stay shrouded, C3 is defensible, and a note saying why helps.
Missing main bonding where services enter is a protective measure completely absent, so it's normally C2. Present but undersized is different: the measure exists and may still work. Measure continuity, and if the resistance is low and the conductor is secure, C3 is common. Look up the conductor sizing requirement in Amendment 4 for your supply and earthing arrangement rather than going from memory, and read how your scheme provider wants it recorded.
FI means you couldn't tell if something is safe, and you need to find out. Use it when an observation can't be coded without more information. It isn't a way of avoiding a decision.
Good reasons for FI:
• You've found a cable going into a wall or floor void you can't trace, and it might be a live undocumented circuit.
• A test result is odd (for example, unexpectedly high earth fault loop impedance on one circuit) and you can't explain it within the inspection.
• Part of the installation wasn't accessible or couldn't be isolated, and you suspect a problem.
Poor reasons for FI:
• You're not sure about C2 versus C3. Decide and explain.
• You didn't have time to finish a test.
• The client wouldn't pay for extra work. If you couldn't inspect part of the installation, that goes under limitations on the report, separately.
FI makes the report Unsatisfactory, so the client sees it. Make clear in the observation text what needs investigating and why. When the investigation is done, you either re-issue or add a follow-on report coded properly.
The rule is simple:
• Any C1, C2 or FI: Unsatisfactory.
• Only C3s, or no observations: Satisfactory.
You don't average or weigh them. A single C2 outweighs ten tidy circuits. Limitations of the inspection (what you didn't inspect or test) are recorded separately and must be agreed with the client in advance, because they affect what the report can say.
For the retest interval, use Guidance Note 3 and the type of premises. That's your recommendation based on condition, so a Satisfactory result with several C3s doesn't need the same recommendation as a clean installation. We haven't repeated the table of typical intervals here because the figures change by premises type; check the current one.
This is a fictional demonstration to show the reasoning, not a real job. A three-bed semi, built in the 1990s, with a split-load consumer unit. Findings:
• No RCD on the socket circuits.
• A cracked double socket in the kitchen, with a hairline crack and one corner missing.
• Main bonding to the water and gas: gas bonding is missing; water bonding is present but the conductor looks small.
Step 1: Socket circuits without RCD. The installation is from the 1990s, when RCD protection of general sockets wasn't a requirement. Check that no sockets are likely to feed outdoor equipment. Find a garage socket on the ground floor ring. The householder says the mower is plugged in there. That moves this from C3 to C2, because the missing additional protection is now tied to realistic outdoor use. Code: C2 for the garage socket circuit. The inspection note records the reasoning. You'd look at the Amendment 4 text and Best Practice Guide 4 to confirm.
Step 2: Cracked kitchen socket. The corner is missing and the shroud around the live terminals is visible through the gap. Someone could touch live parts or push in a pin. Code: C2. If you could see bare live metal, you'd go to C1 and isolate the circuit.
Step 3: Bonding. Gas bonding missing, and the gas pipe enters the kitchen as metalwork: C2. Water bonding present, measured continuity good, conductor possibly smaller than current sizing requirements for the supply. Look up the sizing in Amendment 4. If it's undersized but continuity is good, record a C3 with the measured values and your reasoning.
Result. Two observations are C2 (the garage socket circuit and the kitchen socket), the gas bonding is a third C2, and the water bonding is a C3. Any C2 means the overall result is Unsatisfactory. The report goes to the client with a clear summary, and C2s get a recommendation for urgent remedial work. After the fixes you can issue an EIC or Minor Works certificate for each repair, and if the client wants the EICR to read Satisfactory, you'd carry out a further inspection and issue a new report rather than editing the old one.
In Zappy's EICR tool you can photograph the board so the AI drafts the circuit schedule, with Max Zs looked up for each circuit, then add observations with codes and sign and send the PDF. You still check every circuit and every code yourself. The draft is a starting point, not a decision.
These are common coding problems to avoid. Check your own scheme provider's assessment criteria for what they look for.
• Codes with no reasoning. "C2, no RCD" tells the reader nothing. Say where, what's affected and why you chose the code.
• Coding against today's standard alone. A failure to meet Amendment 4 isn't a C2 by default. Say what the installation was built to, if known.
• Using FI as a dodge. If you can make a decision, make it. FI is for genuine unknowns.
• Inconsistent coding on one report. Missing RCDs coded C3 on one circuit and C2 on a similar one, with no explanation, looks careless.
• Ignoring test results. An observation of "bonding present" with an unrecorded or poor continuity value won't stand up.
• Treating limitations as observations. If you didn't inspect the loft, that's a limitation, not an FI.
• Obsolete edition on the certificate. From 15 October 2026, citing BS 7671:2018+A2:2022+A3:2024 is out of date. Quote BS 7671:2018+A4:2026.
• Satisfactory with a C2 present. Check the final result matches the codes before you send.
• No follow-up on C1. Record what you did on site and who you told, and when.
Can an EICR be Satisfactory with C3s on it? Yes. C3 is a recommendation, and the overall result is Satisfactory if there are no C1, C2 or FI observations. Record each C3 clearly so the client can decide what to do.
Is missing RCD protection on sockets always a C2? No. It depends on the installation's age, location and likely use. Older installations without RCDs often get a C3, with C2 where outdoor use or concealed cables make the risk higher. Check Best Practice Guide 4 and the Amendment 4 text.
Do I code against the current edition or the one the installation was built to? Both matter. Compare against the current BS 7671:2018+A4:2026, but remember standards aren't retrospective, so a departure isn't automatically a C2. Judge the actual risk in the installation as it stands today.
What's the difference between FI and a limitation? FI is something you found and can't yet assess. A limitation is something you agreed not to inspect or couldn't access. Limitations are recorded on the report separately from observations.
What happens after I issue an Unsatisfactory EICR? The client should arrange remedial work for the C1 and C2 items and complete the investigation for any FI. The usual route is to certify the repairs and then, if a clean report is needed, carry out a further inspection and issue a new EICR. If you're comparing software for this workflow, see our notes on what to check before you pick EICR software.
Should I mention my scheme provider's guidance in the report? You don't have to cite it, but you should follow it. If your provider has specific coding guidance for a finding, use that wording in your reasoning so assessors can see how you got there.